STS-6000K-H1
Robust design against harsh environments Innovative cooling design, easy maintenance Comprehensive tests from components, device to solutions
Prefabricated and pre-tested, no onsite internal cabling Compact 20’HC container design for easy transportation
Real-time monitoring of transformer, LV and MV switchgear 0.2% high precision of electricity parameters collection Remote control of ACB and MV Circuit Breaker

Input your details to have a sales representative reach out

Indicate Interest-Solar
Input

Available Inverters

SUN2000-185KTL-H1

AC Power

6,300 kVA @40℃ / 5,400 kVA @50℃1

Max. Inverters Quantity

36

Rated Input Voltage

800 V

Max. Input Current at Nominal Voltage

2 * 2428 A

LV Panel Type

ACB (2500 A / 800 V / 3P, 2*1 pcs), MCCB (250 A / 800 V / 3P, 2*18 pcs)

Output

Rated Output Voltage

10 kV, 22 kV, 30 kV, 30 kV, 30 kV, 35 kV

Frequency

50 Hz, 50 Hz, 50 Hz, 50 Hz, 50 Hz, 60 Hz, 50 Hz

Transformer Type

Oil-immersed, Conservator Type

Tappings

± 2 x 2.5%

Transformer Oil Type

Mineral Oil

Transformer Vector Group

Dy11-y11

Minimum Peak Efficiency Index

In accordance with EN 50588-1

Transformer Load Losses

49.7 kW, 49.7 kW, 49.7 kW, 49.7 kW, 41 kW, 49.7 kW

Transformer No-load Losses

4.8 kW, 4.8 kW, 4.8 kW, 4.8 kW, 5.8 kW, 4.8 kW

Impedance

7.5% (0 ~ +10%) @6300 kVA

MV Switchgear Type

SF6 Gas Insulated, 3 Feeders

Auxiliary Transformer

5 kVA, Dyn11, Ratio Varies according to Customization

Protection
Protection Degree of MV & LV Room
IP 54

Internal Arcing Fault MV Switchgear

IAC A 20 kA 1s

LV SPD

Type I+II

General

Dimensions (W x H x D)

6,058 x 2,896 x 2,438 mm (20’ HC Container)

Weight

< 22 t

Operating Temperature Range

-25℃ ~ 60℃2 (-13°F ~ 140°F)

Relative Humidity

0% ~ 95%

Max. Operating Altitude

2000 m, 2000 m, 2000 m, 2000 m, 2000 m, 2500 m, 2000 m

Applicable Standards

IEC 60076, IEC 62271-200, IEC 62271-202, EN 50588-1, IEC 61439-1

Features

Auxiliary Transformer(50 kVA, Dyn11)

Optional3 , Ratio Varies according to Customization

1.5 kVA UPS

Optional3

Updated to CVC or CCV MV Switchgear

Optional3

IMD

Optional3

STS Interlocking

Optional3

1.  More detailed AC power of STS, please refer to the de-rating curve.

 2. When ambient temperature ≥55℃, awning shall be equipped for STS on site by customer.

3. Extra expense needed for optional features which standard product doesn’t contain.

STS-6000K-H1